600/1000V multiconductor Type T/N control cables

Construction

Conductor:Stranded copper conductor tin or alloy coated where necessary for the application , conductor per

ASTM or IEC 60228.

Separator tape: optional

Insulation: Polyvinylchloride(PVC)/nylon according to IEEE 1580 2010 Type T/N,Type X, E, T, S, P, LSX and LSE

as option.

Shielding: optional

Jacket: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P or

TPO jacket as option (optional for Type P with HD thicknesses).

Armor: optional and shall be nonmagnetic

Sheath: Thermosetting Polychloroprene(neoprene) according to IEEE 1580 2010 Type N, Type T, CP, CPE, L, P

or TPO sheath as option (optional except for tinned copper braid armoured cables).

Optional: For halogen-free constructions, Type LSX, LSE or LSS insulation shall be used with a Type L or TPO

jacket/sheath.

Table B.9—Typical dimensions and weights; multiconductor control 600/1000 V; Type T/N cables


Number of conductors
Conductor
AWG size
Unarmored Armored Armored and sheathed
Nom. dia. (in) Approx. weight (lb/1000 ft) Nom. dia. (in) Approx. weight (lb/1000 ft) Nom. dia. (in) Approx. weight (lb/1000 ft)
2 18 0.28 38 0.34 54 0.44 92
3 18 0.29 47 0.35 63 0.45 102
4 18 0.32 59 0.38 77 0.47 114
7 18 0.37 88 0.43 109 0.56 171
19 18 0.58 221 0.64 252 0.77 340
24 18 0.67 273 0.73 308 0.9 441
30 18 0.71 329 0.77 366 0.94 506
37 18 0.76 391 0.82 431 0.99 579
40 18 0.82 427 0.88 470 1.04 618
61 18 0.98 648 1.04 698 1.21 883
2 16 0.32 49 0.38 67 0.48 108
3 16 0.34 62 0.4 80 0.49 119
4 16 0.37 77 0.43 98 0.55 155
7 16 0.43 116 0.49 140 0.62 209
10 16 0.57 176 0.63 207 0.76 294
14 16 0.62 230 0.68 263 0.8 349
16 16 0.65 255 0.71 288 0.88 418
19 16 0.68 303 0.74 338 0.91 473
24 16 0.79 362 0.85 402 1.02 555
30 16 0.88 473 0.94 518 1.11 686
37 16 0.94 558 1 605 1.17 782
40 16 1.01 606 1.07 659 1.24 848
61 16 1.16 866 1.22 928 1.39 1142
7 14 0.46 155 0.52 182 0.65 256
10 14 0.61 232 0.67 265 0.8 357
14 14 0.66 305 0.72 340 0.89 472
16 14 0.7 345 0.76 380 0.93 519
19 14 0.73 412 0.79 449 0.96 593
24 14 0.89 527 0.95 572 1.12 742
30 14 0.94 635 1 682 1.17 859
37 14 1.01 761 1.07 814 1.24 1003
40 14 1.09 829 1.15 885 1.32 1088
61 14 1.25 1195 1.31 1260 1.48 1489

NOTE—These values are for reference purposes only and should not be construed as requirements. Dimensions are based on the use of Class B conductors. Weights of armored constructions are based on aluminum braid armor. It is recommended that the user/specifier contact the manuf acturer for manufacturer specific values.